Marine Guidance Note

MGN 355

Maintenance of fixed bulk dry powder fire systems

In force
In force
Version
As first issued
Published
30 November 2007
Applies to
Merchant ships
Topics
Safety equipment · Survey and certification

xplor’s summary, not the official text

MGN 355 (M) draws attention to the Administration's guidelines on periodic inspection, testing and maintenance of fixed bulk dry powder fire extinguishing systems. It sets out annual inspections by an accredited service agent, with limited exceptions for trained crew under senior officer supervision, two-yearly tests including nitrogen blow-through and moisture testing of powder, and hydraulic testing of powder containment vessels at intervals not exceeding 10 years. It is addressed to designers, builders, companies, and masters and officers of ships. The notice was published in November 2007.