Marine Guidance Note

MGN 452

Potential hazards of arc flash

In force
In force
Version
As first issued
Published
1 June 2012
Applies to
Merchant ships
Topics
Safety equipment

xplor’s summary, not the official text

MGN 452 (M) warns of the hazards of arc flash associated with high and low voltage electrical equipment on vessels, following a 2011 passenger ship harmonic filter explosion. It advises that work should only be done on de-energised equipment placed in an electrically safe condition, and that control measures such as remote switching and arc detection come before protective clothing and PPE. It also covers incident energy, approach boundaries, and training for everyone working near energised conductors. It is addressed to shipowners, operators, masters, officers, designers, shipbuilders and electrical equipment manufacturers.

Written by xplor from the notice's text on 17 November 2026. It is a summary, not the notice: rely on the official text.

Sections of the notice

  1. 1. Introduction/Background
  2. 2. Phenomenon of arc-flash
  3. 3. Incident energy
  4. 4. Arc flash hazard calculation³
  5. 5. Arc flash and shock protection boundaries
  6. 6. Control measures to be considered to reduce the risk of an arc flash
  7. 7. Protective clothing and personal protective equipment (PPE)
  8. 8. Arc flash and electrical safety training
  9. 9. Electrically safe working condition
  10. 10. Definitions

The notice's own headings. The text of each is in the official notice on GOV.UK.