AFF-M2 · Controlling the space · AFF-M2-A Ventilation, fuel and electrical isolation, and fixed extinguishing systems.

Starve it and make it safe: **fuel shut-offs, electrical isolation** and keeping the fire pump alive.

Fuel and electrics

Governing: STCW Code Table A-VI/3. Builds on: L1.2.

Table A-VI/3 requires knowledge of control of fuel and electrical systems. In practice most serious yacht fires involve one or both: a fuel leak on a hot surface in the engine room, or an electrical fault in a switchboard, AV rack, laundry or battery installation.

Fuel: starve the fire

Before a team goes near a machinery space fire, the engineer should:

  1. Stop fuel transfer and purifier pumps.
  2. Close remote quick-closing valves on tanks supplying the space, from their position outside it.
  3. Stop machinery in the space if the master agrees; on passage this is a navigational decision.
  4. Isolate lube oil and hydraulic pumps that could spray onto hot surfaces.
  5. Report completion to the on-scene commander, who records the time.

Other fuel sources on yachts:

  • Tender and toy fuel: portable cans and fixed tender tanks in the garage.
  • Galley gas, where fitted.
  • Helicopter fuel on yachts with a helideck and refuelling.

Electrics: remove ignition and protect crews

Aim Action
Remove ignition source Isolate the affected circuit or distribution board
Protect firefighters Prove isolation before using water on electrical equipment
Keep life safety Maintain fire pumps, emergency lighting, alarms, PA
Keep manoeuvring Retain steering and navigation power if at sea

The REG Yacht Code builds in some of this. Under Part A 13.4, for yachts of 500 GT and over, a power-operated rescue boat crane must work by hand or from an emergency source in a main power failure, and power-operated shell doors and other obstructions to launching need main and emergency supplies unless they can be worked manually. If your fire takes out main power, those arrangements are what get your rescue boat away.

Shore power

Alongside, a fault may be fed from ashore. Isolate the shore supply at both ends: the ship's breaker and the pedestal. Confirm what now feeds the fire pump.

Batteries

Large lithium-ion banks for hybrid propulsion or hotel load, and small cells in toys and handheld devices, need their own isolation steps in the pre-plan. A battery fire may continue with the circuit isolated, because the energy is inside the cell. Expect prolonged cooling, toxic gas and re-ignition.

WARNING - Water and live equipment Do not direct a water jet at electrical equipment until isolation is proven. Use CO2 or a suitable clean agent on live equipment, and keep the BA team clear of fallen cables.

Who does what

The engineer on watch performs isolations; the on-scene commander authorises them; the bridge logs them. Isolations must be reported, recorded and reversed deliberately afterwards, not by whoever happens to be nearest.

TIP - Label the kill points Mark remote fuel valve pulls and ventilation stops on deck with photoluminescent labels, and make sure deck officers, not just engineers, can find them in smoke.

Practice questions

5 questions

recall · core

Table A-VI/3 lists which of these under control of fire-fighting operations? (a) Bunker sampling (b) Cargo tank inerting (c) Hull cathodic protection (d) Control of fuel and electrical systems

recall · core

Which supplies should remain available when isolating electrical power to a fire zone? (a) Galley equipment (b) Guest AV systems (c) Fire pumps, emergency lighting and alarms (d) Stabilisers

recall · core

Before committing a team to a machinery space fire, the engineer should first: (a) Start the fuel purifier (b) Stop fuel transfer pumps and close remote quick-closing valves on tanks feeding the space (c) Open all engine room vents (d) Run the main engines to clear smoke

recall · core

Under REG Part A 13.4 for 500 GT and over, power-operated shell doors that obstruct rescue boat launching must have: (a) Only main power (b) No power at all (c) Main and emergency power supply, unless manually operable in main power failure (d) Hydraulic power only

scenario · core

Alongside on shore power, smoke is reported from the switchboard room. Detection shows one zone. What is the correct isolation sequence? (a) Leave shore power connected so the fire pump runs (b) Isolate the shore supply at the ship and ashore, confirm the emergency generator or batteries supply fire pumps and lighting, then attack with a non-conductive medium (c) Spray water into the switchboard immediately (d) Open the switchboard doors to vent heat

Independent study. xplor is not an accredited training provider and awards no certificate or Certificate of Competency. The AFF certificate of proficiency is issued only after completing the practical course, including live fire and breathing apparatus exercises, at an MCA-approved training provider. AI-drafted content pending subject-matter-expert review.