Fixed systems
Governing: STCW Code Table A-VI/3; FSS Code chapter 5 (Resolution MSC.206(81)); REG Yacht Code Part A chapter 15A. Builds on: L2.1, L2.2.
The third AFF competence is to inspect and service fire-detection and fire-extinguishing systems and equipment, covering detection, fixed systems, portable and mobile equipment, pumps, rescue and life-support gear, and statutory and classification survey requirements. The criterion is that all of it stays operationally effective at all times.
What a yacht carries
For yachts under 500 GT, REG Part A Table 15A.1 requires a category A machinery space to have a fixed fire-extinguishing system approved to the FSS Code, plus portable extinguishers for oil fires. Yachts of 500 GT and over follow SOLAS II-2/10 via chapter 15B. Common installations:
| System | Typical use | Key hazard |
|---|---|---|
| CO2 | Engine rooms, generator rooms | Lethal to people |
| Water mist | Machinery, accommodation | Electrical, visibility |
| Clean agent | Switchboard, AV, server rooms | Decomposition products |
| Sprinklers | Accommodation on larger yachts | Water damage, stability |
FSS Code gas system rules (MSC.206(81))
- A pre-discharge alarm is activated automatically (for example by opening the release cabinet) and sounds for as long as needed to evacuate, never less than 20 s before release.
- Controls are readily accessible, simple and grouped where a fire in the protected space will not cut them off.
- Automatic release is not permitted except as the Administration allows.
- Two separate controls: one opens the valve to the protected space, the other discharges the bottles, and they can only be worked in that order. Both sit in a release box for that space; if locked, the key is in a break-glass enclosure beside it.
- For machinery spaces, 85% of the gas can be discharged within 2 minutes.
Worked example: how much CO2?
The Code requires the larger of 40% of the gross volume excluding the casing above the level where its area is 40% or less of the space, or 35% of the gross volume including the casing, with free CO2 at 0.56 m3/kg.
| Step | Working | Result |
|---|---|---|
| 40% case | 0.40 x 330 m3 | 132 m3 |
| 35% case | 0.35 x 420 m3 | 147 m3 |
| Governing volume | larger | 147 m3 |
| Mass | 147 / 0.56 | 262.5 kg |
| Within 2 min | 0.85 x 262.5 | 223.1 kg |
Knowing this lets you sanity-check the installation and understand why a partially open space defeats the system.
The release decision
- Headcount complete and confirmed from the muster.
- Space sealed: doors, skylights, vents and fire flaps closed; fans stopped.
- Fuel shut and machinery stopped.
- Master's order, logged with time.
- Release, then leave it sealed. Monitor boundary temperatures and keep cooling.
WARNING - Premature re-entry Opening the space too early lets air reach hot metal and fuel, and the fire comes back with the CO2 gone. Plan re-entry with BA, charged hoses and a ventilation route that takes gas away from people.
Inspection and survey
Weekly and monthly checks follow the planned maintenance system and the manufacturer; annual servicing and bottle checks are by approved service firms; flag and class survey the installation. Keep records ready for survey and port state control.